Excess power capacitance
A week-long study found why a foundry with 1400 kVAr of capacitors still couldn't hold unity power factor.
- Client
- Grinding media foundry, GVMM Odhav
- Solution
- NITEL PF panel, 1800 kVAr, HT-sensed VAR control
- Payback
- 18 months
Background
A renowned foundry in GVMM, Odhav, manufactures cast-iron grinding media on a 2 MVA contract demand from GEB. It runs a 2-tonne induction furnace at 585 V with a total load of 1.6 MVA, plus 1000 kVA of auxiliary load including grinders, welding and shot-blasting machines. The plant already had about 1400 kVAr of power capacitors for reactive power management.
Challenge
The plant could not maintain unity power factor on its utility bills.
Solution
NIFA Electronics studied the plant continuously for a week and traced the poor PF to the furnace's sintering process every Saturday, when the plant ran at only 0.3 to 0.4 PF. The client had been trying to correct this with 1400 kVAr of capacitors connected on the auxiliary load section.
NIFA recommended a specially designed 1800 kVAr PF panel: an LT power capacitor bank with automatic, VAR-based control that switches according to load, sensing reactive power demand on the 11 kV HT supply.
Results
With the PF panel installed, the client could recover the investment in just 18 months.
Contact
Let's stabilise your supply.
Share your load and the problem you're seeing. An engineer will get back to you with a recommendation.
Send an inquiry
Goes straight to our sales team.