Energy saving
A NanoVIP load study showed a 60 kW motor running at half load. Right-sizing motors across the plant saved energy without new capacitors.
- Client
- Leading textile mill, Ahmedabad
- Solution
- Elcontrol-Energy NanoVIP portable load manager
- Saving on one motor
- ~Rs. 20,000 per year
Background
One of Ahmedabad's leading textile industries used the Elcontrol-Energy NanoVIP portable load manager to study the loading of motors across its plant. It showed accurately which motors were over-rated in kW. By switching to correctly rated motors, the company saved many times what it had invested in the load manager.
Before
- Motor rating
- 60 kW
- Current (tong tester)
- 104 A
- Assumed normal operating current
- 80 A
- Assumed loading
- 80/104, run this way for years
Many more motors in the plant were in the same situation.
What the NanoVIP showed
Measured with the NanoVIP, the 60 kW motor was drawing only about 30 kW, just 50% of its rated capacity and far below expectations. Poor loading meant poor power factor, which is why the current was high.
After confirming that the production requirement would never exceed 30 kW, the plant replaced it with a 40 kW motor.
Results
- Around Rs. 20,000 a year saved on this one motor
- The study was repeated at every important load point, and correctly rated motors are now used throughout
- Overall plant power factor improved and maximum demand reduced, without adding capacitor banks
The same load manager can also be used to reduce maximum demand, evaluate energy-saving devices, and recommend correct ratings for motors, cables and switchgear.