Overview
Reactive power compensation panels are used to reduce load in the Electrical grid and to save costs. This is the reason, that there are Special requirements for the control units of these compensation panels, the reactive power regulator. The most important task for the reactive power regulator is to control the reliable termination of reactive power. This is reducing the costs for electrical energy. Cables, transformers, switch components and power distribution are unloaded by reduce reactive power. Another task of the reactive power regulator is monitoring the compensation panel and giving alarms. All of these requirements are solved by Beluk reactive power regulators with their patented regulation principle. By continuous measuring of the capacitor power, the steps are always used with their exact capacitor ratings. The regulation program is only defined by the choice of the capacitor sizes. There are no limitations and no settings for step sequence are necessary at BLR-CX. If BLR-CX cannot recognize anymore the function of a step e.g. caused by damaged capacitors, contactors or blown fuses, then it shows alarm. The integrated alarm relay with sign-of-life contact can forward this also to a control room.
Display
BLR-CX is equipped with LCD with backlight. It shows information about the panel and about the mains parameters.
Reported mains conditions
Voltage, Current, kW, kvar, kva, kvar to target, rd th THD U, 3 to 15 harmonic of voltage, cos phi, power factor, frequency, temperature
Reported equipment information
Power-on hours of panel, operating cycles per step, max, percentage rating per step rating per step compared with the nominal rating. Cos phi and status of the exits are shown permanently.
Monitoring
The monitoring features of BLR-CX guarantee a reliable operation and a long life of the compensation panel:
- Low voltage switch - off against chattering of contactors
- Over voltage switch-off for protecting the capacitors
- Over temperature switch-off
- Monitoring of THDU
- Recognition of defective capacitors
- Alarming, when target o regulation cannot b reached
- Signaling of the need for maintenance
- Fan control
Failures and announcements of the panel are shown in LCD Failures can also be forwarded by the volt free alarm-contact (sign-of-life signal) For switching the fan, one of the step-exits has to be used.
Advanced variants
- For real time compensation
- For individual compensation in all 3 phases
- Thyristor switches
Technical specifications
- Type of device
- Power Factor Control Relay (Automatic Reactive Power Management)
- Control variable
- Electrical displacement reactive power
- Principle of Regulation
- Stepped regulation with the following modes : Best-Fit : starting with the biggest exits; LIFO: last in-first out; Comb filter: Best-Fit, with more connected power of odd exits; Progressive: all required exits are switched in quasi one operation
- Special Feature
- Automatic detection and correction of the phase of the phase of current voltage connection; Automatic detection of the used exits; Over-and under voltage monitoring; Monitoring of THD U; Over temperature switch-off
- Measuring Display
- V, A, kVA, kW, kvar, THD U, 3 to 15 harmonic of voltage
- Information Display
- Switch cycles per step, capacitor rating, status of the exits, Operating hours of the panel, max. temperature, average PF
- Measuring & Auxiliary Voltage
- 90-550 V AC,1 Ph,45-65HZ,5VA, max. fuse 6A, VT ratio from 1 to 350.0
- Current Measuring
- 10mA-6 A, 1 Ph, burden 20mOhm, CT ratio from 1 to 4000
- Control Exits
- Upto 14 relay , N/O, volt free with common point, max. fuse 6A,
- Capacity
- 250V AC/5A
- Temperature measuring
- By NTC
- Sign-of-Life contact
- Relay, volt free, N/O, max. fuse 4A, breaking capacity: 250V AC /5A
- Fan Control
- By using a control exit
- Interface
- TTL, rear side
- Ambient Temperature
- Operation: -20 C-70 C, storage:-20 C80C
- Humidity
- 0% -95%, without moisture condensation
- Overvoltage class
- ll , pollution degree 3 (DIN VDE 0110, Teil 1/ IEC60664-1)
- Standards
- DIN VDE 0110 Teil 1 (IEC 60664-1:1992) VDE 0411 Teil 1(DIN EN 61010-1 /IEC 61010-1:2001) VDE 0843 Teil 20 (DIN EN 61326 /IEC 61326: 1997 +A1:1998+A2:2000)
- Conformity and Listing
- CE, UL, Cul
- Terminals
- Plugable terminal blocks, screw type, max. 4qmm
- Casing
- Front: IP50, (IP54 by using a gasket),Rear: IP20
- Weight
- Approx. 0.6kg
- Dimensions
- 144x144x58mm hxwxd, cutout 138 (+0.5) x 138(+0.5)mm
Product brochure
Full specifications for the Beluk PF Relay, ready to share with your team.
Download PDFMore in Power Management
All Power ManagementContact
Let's stabilise your supply.
Share your load and the problem you're seeing. An engineer will get back to you with a recommendation.
Send an inquiry
Goes straight to our sales team.